Select your language

HEINZMANN Company Group

HEINZMANN Electric Drives
Robust electric motors

REGULATEURS EUROPA
Control & Monitoring

HEINZMANN China
Control & Actuation

HEINZMANN Automation
Marine Automation

HEINZMANN UK
Gas & Water Turbine Control

HEINZMANN Australia
Steam Turbine Control

CPK Automotive
Emission Control

Giro Engineering
Diesel Engine Components

HEINZMANN IFT GmbH
Oil Mist Separators and Blow-by Filter Technology

Optimal control technology for any type of gas engine

The basic version of XIOS UC consists of the Main board (MC), extendable by up to 5 extension modules (MA) and an Expander Board MD1 or MD2.

I/O capacity of the Main Board:

Analogue/digital input Digital output Hall pick-up Sensor supply
11x 2x, max. 4A 2x 2x (5 or 12 VDC configurable)

The XIOS Expander boards MD1 or MD2 offer options for connecting further Extension Boards (MA).

I/O capacity of the Expander Board MD1:

Analogue/digital input Digital input Digital output Inductive pick-up Sensor supply Additional slots
8x 2x 2x, max. 4A 2x 1x (5 or 12 VDC configurable) 6x board MA

Board MD2 is required for the XIOSGenSet and XIOSCHP applications.

I/O capacity of the Expander Board MD2: all possibilities of MD1 and in addition

Digital Input Analogue input AVR output Relay output Addtional slots
4x, isolated 6x AC voltage (3x bus und 3x generator)
4x AC phase current, max. 5 A
1x 1x 3x board MA

  Each of the Extension Modules provides 2 (if isolated), 4 or 8 (if input-only) I/O channels, resulting in a great variety of
  configuration options:

Module type Function
 A2 4x analogue or digital output, monitored, 0...5 VDC (11 mA), 0...24 mA
digital output, max. 1 A PWM controlled (0...100 %)
 A3 4x analogue or digital input, 0...5/10/36 VDC, 0...24 mA
temperature input Pt 1000, Pt 200, Pt 100, Ni 1000, NTC
2x sensor supply (5/12 VDC configurable, 50 mA or VBAT)
 A4 2x analogue or digital input, electrically isolated, 0...5/10/36 VDC, 0...24 mA
temperature input Pt 1000, Pt 200, Pt 100, Ni 1000, NTC
2x sensor supply (5 VDC, 50 mA)
 A5 2x analogue or digital output, electrically isolated, 0...5 VDC (2.5 mA), 0...24 mA
digital output: 60 VDC/40 VAC, 400 mA static, optional: 400 VDC/280 VAC, 100 mA
 A6 2x analogue or digital output, electrically isolated, monitored, 0...5 VDC (10 mA), 0...24 mA
 A7 6x digital input, 9...36 VDC
 A8 up to 4x digital output, high or low-side, current read back for control-loop applications, thermal shutdown
 
 A1 2x thermocouple amplifier, electrically isolated, (J/K/E/R/S/B/N), configurable gain and offset
 A9 1x H bridge output, up to 8 A static current, current read back for control-loop applications

XIOSGas takes over the central control of all system functions

  • All in one

    All in one

    The modular and multifunctional controller XIOSGas centrally controls all system functions of a gas engine.
  • Motormanagement

    Engine Management

    • Central Control
    • All functionalities of the gas engine management are taken over
    • The control unit includes speed and mixture control, ignition control, engine monitoring and other functions
  • Air Path Management

    Air Path Management

    XIOSGas takes over the complete management of the air path, such as speed control, the control of actuators, throttle valves, wastegate bypass or the control of EGR systems.
    • Integrated speed control
    • Fast response to speed and load changes
    • Can be combined with all HEINZMANN actuators
  • Air Fuel Ratio Control

    Air Fuel Ratio Control

    • Integrated Air Fuel Ration Control
    • Power, Lambda or NOas feedback signal
    • Coordinated system solutions for different gas qualities
  • Ignition Control

    Ignition Control

    • Ignition control through the HEINZMANN PHLOX system or through the support of third-party systems
    • Speed and power-dependent ignition timing
    • Autopark function to reduce spark plug wear
  • Knock Control

    Knock Control

    • Control of knock monitoring with the HEINZMANN ARIADNE system or by supporting third-party systems
    • Monitoring knocking combustion
    • Ignition timing correction and power reduction

We use cookies on our website. However, non-essential cookies (e.g. tracking cookies) are only set if you consent to their use. We point out that in connection with these cookies, your personal data may be transferred to US service providers and merged with other personal data. In the case of data transfers to the USA, there is a risk that this data will be accessed by US authorities without notification and without any legal remedy. With your consent, you also agree to this data transfers to the USA. For more information on the cookies we use, their purposes and storage periods, please refer to our privacy notice at: www.heinzmann.com/en/privacy-policy.